Shapiro PJM Backstop Costs and Pennsylvania Data Centers
Pennsylvania Gov. Josh Shapiro issued an executive order directing the PUC to assign PJM reliability backstop auction costs to data centers that have not secured their own capacity. PJM faces a 6.8 GW shortfall. PA cultivators still pay PJM capacity in supply, but policy may shift cost allocation away from general C&I load over time.
By Jason Taken, Founder, Jaken Energy
Updated September 12, 2026What Shapiro ordered in August 2026
Pennsylvania Gov. Josh Shapiro issued an executive order directing the Pennsylvania Public Utility Commission to develop rules limiting reliability impacts from data centers [canary-shapiro-eo-2026]. The order codifies standards Shapiro floated in February 2026.
Core requirements for data centers above 25 MW seeking preferential permitting include:
- Secure incremental electric capacity for their full demand, or face curtailment before other customers during emergencies [canary-shapiro-eo-2026]
- Pay grid upgrade costs tied to their service [canary-shapiro-eo-2026]
- Meet rising carbon-free power percentages (10% in 2027 scaling to 32% by 2035) if they sign DEP consent orders [canary-shapiro-eo-2026]
PUC Chair Stephen DeFrank backed the plan, saying Pennsylvanians should not subsidize infrastructure for the world's largest energy users [canary-shapiro-eo-2026].
PJM's 6.8 GW shortfall and backstop auction
PJM's July 2026 proposal addresses data-center-driven load growth by pushing states to decide who pays for emergency capacity [canary-shapiro-eo-2026]. PJM faces an estimated 6.8 GW shortfall in coming years, triggering a proposed reliability backstop auction [canary-shapiro-eo-2026] [pjm-board-letter-2026].
Shapiro's order tells the PUC to ensure utilities charge data centers, not other customers, for backstop costs assigned to them, even if a data center becomes insolvent [canary-shapiro-eo-2026].
For a cannabis cultivator, two channels matter:
- Existing PJM capacity charges already embedded in default supply and many retail contracts
- Future backstop charges if procurement proceeds and state rules assign them
Neither channel reduces PPL or PECO delivery demand charges.
Why grows still care about data center policy
Cannabis facilities are large C&I loads, but they are not typically 25 MW hyperscale data centers. Policy still affects growers because:
- Capacity market forecasts include all new load until segmented
- Transmission upgrades are regionally shared until allocated
- Retail contract pass-throughs may reference PJM regulatory charges broadly
Central PA operators shopping supply around PPL's 12.745¢ June 2026 benchmark should read our PPL price-to-compare post alongside this policy tracker.
| Topic | Cultivator action |
|---|---|
| Default supply | Track June/December PTC resets |
| Retail fixed contract | Read PJM capacity pass-through table |
| Delivery bill | Monitor transmission riders separately |
| Policy | Watch PUC rulemaking on backstop allocation |
Worked example: capacity pass-through sensitivity
Assume a retail contract passes through PJM capacity at actual cost. Inputs we chose.
| Input | Value |
|---|---|
| Monthly kWh | 85,000 |
| Embedded capacity in default | 2.1¢/kWh (illustrative) |
| Default supply @ 12.745¢ PTC | $10,833/month supply [from PPL context] |
| Pass-through adds 0.4¢ if backstop fills | 85,000 × $0.004 = +$340/month |
This illustration is not a published backstop rate; it shows why pass-through language matters when policymakers move costs between customer classes [canary-shapiro-eo-2026].
Fixed all-in contracts may delay pain until renewal. See fixed vs index contracts.
Alignment with PJM's July proposal
Shapiro's curtailment and bring-your-own-power rules mirror PJM's plan to have state-regulated utilities decide which data centers face interruption unless they self-supply capacity [canary-shapiro-eo-2026]. Illinois ComEd proposed an interruptible data center tariff in the same vein [canary-shapiro-eo-2026].
Maryland cultivators seeing transmission spikes should read Maryland OPC on PJM transmission costs for the delivery-side parallel.
Practical steps for PA operators
- Under Pennsylvania switching, compare retail offers with explicit PJM capacity tables.
- Model default supply using Pennsylvania commercial rates as context, not as a substitute for your bill.
- Monitor PUC rulemaking implementing Shapiro's order for backstop cost assignment language.
- Keep demand management (staggered lights, HVAC sequencing) focused on utility delivery tariffs you cannot shop away.
Policy may shift who pays for the next increment of PJM procurement [canary-shapiro-eo-2026]. It does not remove capacity charges from the market. Cultivators should contract with eyes open on pass-throughs and reset dates, not assume data center rules automatically lower grow supply rates overnight.
Consent order path vs business-as-usual siting
Shapiro's order offers preferential permitting for data centers signing DEP consent orders with bring-your-own-power commitments [canary-shapiro-eo-2026]. Facilities that skip consent face longer reviews and potential local opposition [canary-shapiro-eo-2026].
Cannabis facilities operate under separate state licensing but share PJM capacity math with any new large load. Local zoning hearings increasingly reference grid cost allocation language from data center debates.
Carbon-free percentage schedule
Consent-order data centers must hit 10% carbon-free power in 2027, rising to 32% by 2035 [canary-shapiro-eo-2026]. Cultivators buying 100% renewable retail supply for branding should verify RPS vs voluntary REC claims separately from this data center policy.
Massachusetts 100% renewable waiver rules for lighting limits differ; see REC guidance if you operate multi-state.
Sierra Club diesel backup concern
Separate legislation would limit diesel generators data centers use during curtailment events [canary-shapiro-eo-2026]. Cultivators with backup gensets for crop protection should not assume diesel policy tracks data centers exactly, but air quality enforcement trends are worth monitoring with counsel.
Practical contract clause search
Search retail supply PDFs for:
- Regulatory change in law
- Material adverse change in ISO rules
- Capacity pass-through definitions referencing RPM or backstop
If a clause allows unilateral supplier adjustment, model worst-case adders before signing through 2028 PJM capacity cycles discussed in industry reporting [canary-shapiro-eo-2026].
Data Center Coalition response
The Data Center Coalition supported Shapiro's order framework while warning against midstream rule changes for projects already underway [canary-shapiro-eo-2026]. Cannabis operators are not coalition members, but retroactive regulatory risk language in supply contracts should be read in the same spirit.
The 25 MW threshold and why cultivators sit below it
Shapiro's order targets data centers above 25 MW seeking preferential permitting [canary-shapiro-eo-2026]. A 500 kW cannabis flower room is large by horticulture standards but an order of magnitude below the 25 MW line. You will not receive data-center minimum charges or curtailment-first treatment under this order.
You still pay PJM capacity embedded in PPL, PECO, and Duquesne default supply because capacity markets price regional margin, not individual customer class [canary-shapiro-eo-2026]. Policy that shifts backstop auction costs to data centers may eventually lower capacity forecasts for everyone else, but timing is uncertain. Contract for pass-through transparency now rather than assuming future political wins.
PJM board letter and the 6.8 GW shortfall timeline
PJM's May 2026 board letter to governors described a 6.8 GW shortfall in accredited resources relative to load forecasts, triggering discussion of a reliability backstop auction [pjm-board-letter-2026]. The letter asked states to decide cost allocation before emergency procurement proceeds [canary-shapiro-eo-2026].
Pennsylvania cultivators should read the letter's appendix tables with counsel if your retail contract includes regulatory change in law clauses. A backstop charge assigned to data centers only under Shapiro's PUC rules may not appear on your bill; a broad RTO allocation would [canary-shapiro-eo-2026] [pjm-board-letter-2026].
PECO quarterly resets versus PPL semiannual calendars
Pennsylvania utilities reset default supply on different calendars as described in our PPL June 2026 price-to-compare post. PECO moves quarterly; PPL moves June 1 and December 1. Philadelphia-area grows and Central PA grows therefore hit capacity-driven supply changes on different months even when PJM capacity is identical [canary-shapiro-eo-2026].
MSOs should maintain a procurement calendar by meter, not by state. Compare Pennsylvania commercial electricity rates for context and Pennsylvania switching steps for enrollment mechanics.
Carbon-free percentage schedule for consent-order data centers
Consent-order data centers must hit 10% carbon-free power in 2027, rising to 32% by 2035 [canary-shapiro-eo-2026]. Cultivators buying 100% renewable retail supply for branding should verify RPS versus voluntary REC claims separately from this data center policy. See renewable energy certificates for cannabis brands.
Contract clause search before 2028 capacity cycles
Search retail supply PDFs for regulatory change in law, material adverse change in ISO rules, and capacity pass-through definitions referencing RPM or backstop [canary-shapiro-eo-2026] [pjm-board-letter-2026]. Clauses allowing unilateral supplier adjustment require worst-case adder modeling before signing through 2028 PJM capacity cycles discussed in industry reporting [canary-shapiro-eo-2026].
Diesel backup and air quality trends
Separate legislation would limit diesel generators data centers use during curtailment events [canary-shapiro-eo-2026]. Cultivators with backup gensets for crop protection should confirm air quality rules with counsel; diesel policy may not track data centers exactly but enforcement trends matter for outage planning [canary-shapiro-eo-2026].
Data Center Coalition retroactive risk framing
The Data Center Coalition supported Shapiro's framework while warning against midstream rule changes for projects already underway [canary-shapiro-eo-2026]. Cannabis operators are not coalition members, but retroactive regulatory risk language in supply contracts should be read in the same spirit before 2027 PUC rules publish [canary-shapiro-eo-2026] [pjm-board-letter-2026].
Local zoning and grid cost allocation hearings
Cannabis facilities operate under separate state licensing but share PJM capacity math with any new large load [canary-shapiro-eo-2026]. Local zoning hearings increasingly reference grid cost allocation language from data center debates; engage early if expanding MW-scale processing [canary-shapiro-eo-2026].
Practical steps for PA operators this quarter
- Under Pennsylvania switching, compare retail offers with explicit PJM capacity tables [canary-shapiro-eo-2026]
- Model default supply using Pennsylvania commercial rates as context, not as a substitute for your bill [canary-shapiro-eo-2026]
- Monitor PUC rulemaking implementing Shapiro's order for backstop cost assignment text [pjm-board-letter-2026]
- Keep demand management focused on utility delivery tariffs you cannot shop away [canary-shapiro-eo-2026]
Policy may shift who pays for the next increment of PJM procurement [canary-shapiro-eo-2026]. Cultivators should contract with pass-through eyes open, not assume data center rules automatically lower grow supply rates overnight [pjm-board-letter-2026].
Frequently asked questions
What is PJM's reliability backstop auction?
PJM proposed an emergency procurement to cover an estimated 6.8 GW shortfall in coming years. Utilities would bid for resources; costs would flow to customers unless states assign them differently.
Does Shapiro's order protect cannabis businesses from backstop charges?
The order directs the PA PUC to assign backstop costs to data centers that have not secured incremental capacity, not to shift them broadly to other customers. Cultivators are not named as exempt; the aim is to stop general ratepayers from subsidizing hyperscale load.
Do data centers have to curtail before other customers?
Shapiro's order aligns with PJM proposals requiring utilities to curtail data centers before other customers unless a data center secured its own incremental capacity.
How does this relate to my retail supply contract?
If your contract passes through PJM capacity or regulatory charges, backstop outcomes may appear as adjustments. Fixed all-in contracts may exclude or include them depending on fine print.
Are other PJM states doing the same?
Illinois, Indiana, New Jersey, Ohio, and Virginia are among states pursuing data center cost-allocation laws, but Pennsylvania's executive order explicitly tasks the PUC with backstop cost assignment.
Related reading
- How to Switch Electricity Suppliers in Pennsylvania: A Step-by-Step Guide for Cannabis Businesses
How a PECO, PPL, or Duquesne business enrolls with a PUC-licensed EGS: eligibility, Price to Compare, enrollment, meter-read timing, and contract rules.
- Pennsylvania Commercial Electricity Rates for Cannabis Facilities: EDC Classes, Benchmarks, and Bill Drivers
Pennsylvania commercial power prices vs. the U.S., PECO PPL and Duquesne delivery classes, Price to Compare benchmarks, and PJM capacity context.
- Fixed vs. Index vs. Block-and-Index Electricity Contracts
What each supply structure means, who carries price risk, which fits a 24/7 grow load, what pass-throughs do, and a worked 12-month comparison.
- PPL June 2026 Business Price-to-Compare 12.745¢ and $275M Distribution Settlement
PPL Electric's June 2026 business price-to-compare is 12.745¢/kWh with a $275M distribution settlement filed March 2026. Central PA cultivator contract timing.
- Maryland OPC Rising PJM Transmission Costs
Maryland OPC March 2026 report: transmission is ~10% of bills, $5.4B new PJM projects allocated to Maryland. Line cultivators cannot shop away.
Jason Taken founded Jaken Energy, the commercial energy procurement practice behind this site. He works with licensed cannabis operators in deregulated electricity markets to lower supply rates, manage demand charges, and evaluate efficiency upgrades.