Skip to content

Demand Charge Questions for Cannabis Facilities

A demand charge bills you for your highest average power draw in a single 15- or 30-minute interval each month, not for total kilowatt-hours. Indoor cannabis facilities hit high demand because lighting, HVAC, and dehumidification peak together when rooms switch on. Depending on the tariff, demand can be 30 to 70 percent of a commercial bill. Ratchets, load factor, and coincident peaks like ERCOT 4CP add layers a supply contract cannot fix.

By Jason Taken, Founder, Jaken Energy

Updated September 12, 2026

kW vs kWh on a grow bill

Energy is kilowatt-hours: how much you used over the month. Demand is kilowatts: how fast you drew power at your worst interval. NREL's tariff survey describes utilities averaging load over 15- or 30-minute windows and billing the highest window as demand [nrel-demand-charge-survey].

A facility that runs 400 kW flat for twelve hours and idles at 100 kW overnight uses a lot of kWh but peaks at 400 kW. A facility that hits 550 kW for one interval because every flower room and every chiller starts together uses fewer kWh but pays a higher demand charge. Utilities price the infrastructure for the peak.

Why cannabis peaks are tall

The Northwest Power and Conservation Council's survey of licensed producers found lighting at 66 percent of electricity use, flowering rooms at 49 percent, cooling at 15 percent, and dehumidification a major share of the HVAC slice [nwpcc-cannabis]. A photoperiod is a timer, not a dimmer. Contactors close and the load appears inside one interval. HVAC responds to the heat seconds later. The spike is structural.

NREL's survey of more than 10,000 tariffs found demand can be 30 to 70 percent of a commercial bill [nrel-demand-charge-survey]. Grows with high watts per square foot and synchronized schedules sit at the high end of that range when the tariff carries a double-digit per-kW charge.

Ratchets and load factor together

Ratchet sets a floor from history. Indiana Michigan Power billing demand shall not be less than 60 percent of the highest peak in the prior eleven months [im-tariff-iurc]. Santee Cooper uses 30 percent [santee-cooper-demand]. One bad test day where every room runs can raise the floor for a year.

Load factor compares average to peak. EIA defines load factor as an indicator of how evenly electricity is consumed [eia-glossary-l]. Indoor cannabis with twelve-on, twelve-off lighting often shows load factors that look fine on paper but still produce expensive peaks because the peak interval is so much taller than the off-peak trough.

MetricFormula (conceptual)What a low value signals
Load factorAverage kW ÷ Peak kWSharp spikes; demand-heavy bill
Ratchet floor% × Highest peak in lookbackBill stays high after a cutback month
Coincident peakYour kW at grid peak hourDrives capacity/transmission, not just utility demand

Use the demand charge estimator with your own interval data where available.

What a supply contract does not fix

Switching to a competitive supplier does not change the utility's distribution demand charge. A fixed supply contract locks or floats the generation price; it does not reclassify your meter or remove a ratchet.

In PJM, NYISO, and ISO-NE, coincident peak behavior on your meter also sets capacity tags that flow through supply bills. That is supply-side peak cost, managed by scheduling and curtailment, not by choosing a different REP name.

Texas adds ERCOT 4CP: ERCOT describes using the highest-load 15-minute intervals in each summer month to allocate transmission costs [ercot-dr-overview-2023]. A North Texas grow on a transmission-voltage schedule may care as much about four summer afternoons as about its own monthly utility demand peak.

Scheduling and equipment levers

Stagger photoperiods across flower rooms so coincident lighting plus HVAC stays below a single-room peak. Biology allows different rooms on different twelve-hour windows.

LED retrofit lowers watts per square foot if you do not add fixtures to compensate. See LED vs HPS.

Rate class review with the utility sometimes matters more than supplier shopping. Moving from a general service tier with a demand ratchet to a larger-load schedule with different demand rules is a utility tariff conversation. See utility rate classes.

Batteries can shave a short interval if demand charges exceed roughly 15 dollars per kW in NREL's storage screening range [nrel-demand-charge-survey]. A thirty-minute lighting spike is an easier battery target than a twelve-hour plateau. Match battery discharge duration to your tariff's billing interval, whether 15 or 30 minutes [nrel-demand-charge-survey].

Demand response programs pay some facilities to curtail during grid peaks. Enrollment rules vary by utility and ISO. A grow that can dim or delay non-critical load for an hour may earn more from a DR event than it saves on one month's demand line, but photoperiod constraints limit how often that works.

The long-form walkthrough is on demand charges explained and peak demand vs. peak usage. For bill-wide strategy, see how to lower a grow facility electric bill.

Reading interval data for your peak interval

Most commercial demand meters record usage in 15-minute intervals. Your utility bill shows the billed demand in kW; interval data shows which clock period set that number. Export twelve months from the utility portal or ask your supplier for Green Button data if available.

Look for three patterns on cultivation accounts:

  1. Lights-on step. A vertical jump at photoperiod start when contactors close.
  2. HVAC lag. A second bump five to fifteen minutes later when compressors respond to sensible load.
  3. Batch overlap. Extraction or drying equipment stacking on top of horticultural load.

Staggering addresses pattern one and often pattern two. Pattern three appears in mixed-use buildings where kitchen or lab load shares the meter with flower rooms.

Demand charge as dollars per pound

Operators sometimes normalize demand cost against production. Assume peak demand of 550 kW, a delivery demand charge of $14 per kW (tariff input), and annual dry yield of 18,000 pounds (inputs). Monthly demand cost is 550 x $14 = $7,700. Annualized demand is $92,400. Demand cost per pound is $92,400 / 18,000 = $5.13 per pound before energy.

Cutting peak to 480 kW saves 70 x $14 = $980 per month, or about $0.65 per pound at the same yield. That math helps a CFO compare demand work to wholesale flower price moves.

When batteries pencil for cultivation peaks

NREL's storage screening work identified millions of commercial customers where demand charges above roughly $15 per kW can support behind-the-meter battery economics [nrel-demand-charge-survey]. A grow with a sharp thirty-minute lighting spike at lights-on is a better battery candidate than one with a twelve-hour flat plateau. Match battery discharge duration to the utility billing interval, whether 15 or 30 minutes [nrel-demand-charge-survey].

Federal tax credit eligibility for cannabis entities remains limited while marijuana is federally controlled. Model battery payback on utility savings alone unless your tax advisor confirms ITC eligibility.

Coincident peak on the supply side in PJM

Utility distribution demand and ISO coincident peak behavior are related but billed differently. Your highest interval in the month sets utility delivery demand on many tariffs [nrel-demand-charge-survey]. Your average load during PJM's five Coincident Peak hours sets a peak load contribution tag that flows through capacity charges on supply bills [pjm-glossary]. Staggering flower rooms helps both if it lowers your meter's contribution during those grid peak hours. Running everything at night may lower one without lowering the other.

Pull twelve months of interval data before you assume which peak matters more for your facility. A North Jersey grow on PSEG delivery may care about both the utility ratchet and the PLC tag. See peak demand vs. peak usage.

Worked demand example for a staggered grow

Assume four flower rooms at 100 kW each and HVAC that adds 40 kW within ten minutes of lights-on (inputs). Synchronized schedule: one interval near 440 kW. Staggered two-by-two with two-hour offset: first interval near 240 kW, second interval near 240 kW if HVAC follows each block separately. Billed demand on a ratchet-free tariff is the maximum interval, so stagger wins when peaks decouple.

At $14 per kW delivery (tariff input), the synchronized case pays 440 x $14 = $6,160 per month on demand alone. The staggered case at 240 kW pays $3,360, saving $2,800 per month with nearly identical kWh. Run your interval curve before you assume stagger helps; if HVAC is central plant, peaks may stay stacked [nrel-demand-charge-survey].

Ratchet illustration with eleven-month lookback

Assume 600 kW peak in July and a 60 percent ratchet [im-tariff-iurc]. Floor becomes 360 kW billed through the following June even if measured demand falls to 280 kW in January. At $14 per kW, you pay on 360 kW, not 280 kW, an extra 80 x $14 = $1,120 that month versus a no-ratchet tariff. One bad commissioning test where every room runs together can cost $1,120 x 12 = $13,440 annualized until the lookback clears.

Quick reference: questions to ask your utility account manager

  1. What interval length sets billed demand, 15 or 30 minutes?
  2. Is there a ratchet and what percent lookback applies?
  3. Does my class bill on-peak demand separately from maximum demand?
  4. Will a rate class change require a new service agreement or witness test?
  5. Can I get Green Button interval data for the last twelve months?

Write down the answers before you spend capex on batteries or LEDs aimed only at kWh. The demand charge estimator turns your peak kW and tariff into dollars so you can compare levers on one page.

Frequently asked questions

What is a demand charge and how is it measured?

A demand charge is a fee based on your highest average power in kilowatts during a fixed interval within the billing period, usually 15 or 30 minutes, not on total kilowatt-hours. NREL's survey of utility tariffs describes billing demand as the peak kW in those windows. Santee Cooper bills on the maximum 30-minute demand in the period. The utility sizes wires and transformers for that peak whether it lasts one interval or all month, so the charge allocates infrastructure cost to customers who create spikes.

Why can demand be 40 to 60 percent of a grow's bill?

Because lighting and HVAC stack on the same interval. NREL found demand can account for 30 to 70 percent of a commercial customer's bill depending on tariff. The Northwest Power and Conservation Council survey found lighting was 66 percent of electricity use at licensed indoor producers, with flowering rooms alone at 49 percent. Hundreds of kilowatts of lights switch on together and compressors follow. Two facilities with the same monthly kWh can pay very different demand charges if one's load is flat and one's peaks sharply.

What is a ratchet clause?

A tariff rule that sets a floor on billed demand based on past peaks. Indiana Michigan Power's schedules provide that billing demand shall not be less than 60 percent of the highest monthly billing demand established during the past 11 months. Santee Cooper uses 30 percent of the highest billed demand from the previous 11 months. If you hit 600 kW in July, a 60 percent ratchet bills at least 360 kW every month through the following June even if you fallow rooms and measure 250 kW.

What is load factor and how do I improve it?

Load factor is average load divided by peak load over a period. EIA defines load factor as a measure of how evenly electricity is consumed. A grow with lights on twelve hours and off twelve has a lower load factor than a flat industrial load, which means more demand charge per kWh consumed. You improve it by flattening peaks: stagger room photoperiods, ramp HVAC where controls allow, shed non-critical load at the peak interval, or shift batch equipment in extraction. You rarely improve it by using less total energy without touching the peak interval.

Does a fixed supply contract cover demand charges?

No for utility delivery demand. Distribution demand is a regulated wires charge and stays on the utility bill whether you shop supply or not. A fixed supplier contract covers the generation price you agreed to; it does not cap the utility's per-kW delivery fee. In PJM states a contract may fix or pass through capacity costs tied to your coincident peak, which feels like demand but sits on the supply side. Read both the utility tariff and the supplier contract.

How do I stagger rooms to avoid coincident peaks?

Offset photoperiod start times so all flower rooms do not energize in the same 15-minute window. If two 200 kW rooms share a schedule, coincident peak is roughly 400 kW plus HVAC. Offset by 30 to 60 minutes and the meter may record two lower peaks in different intervals, though the monthly billed demand is still the highest single interval. Also stagger veg flip days and maintenance tests where every ballast fires at once. Interval meter data shows which minute sets the peak.

Does LED reduce kW demand or just kWh?

Both, if fixture wattage drops. LED retrofits cut watts per square foot, which lowers the lighting block of the peak. They also cut kWh over the photoperiod. HVAC and dehumidification load may fall with lower heat output, which can shrink the stack at lights-on. If you replace HPS one-for-one with the same circuit count but lower wattage, demand falls proportionally. If you add more fixtures to hit higher PPFD, demand may not fall. See the LED vs HPS page for energy math.

What is ERCOT 4CP?

Four Coincident Peak is a Texas transmission cost allocation method. ERCOT's demand response overview describes using the highest-load 15-minute settlement intervals in each of the four summer months to set transmission charges for certain customers. Your average kW during those four grid peak intervals drives the following year's transmission multiplier. Curtailing during those intervals can reduce next year's TDU transmission charge; it is separate from the utility distribution demand charge and from your REP energy contract.

About the author
Jaken Energy

Jason Taken founded Jaken Energy, the commercial energy procurement practice behind this site. He works with licensed cannabis operators in deregulated electricity markets to lower supply rates, manage demand charges, and evaluate efficiency upgrades.

Sources

Inline citations in this article, such as [nrel-demand-charge-survey], refer to the entries below. Links open the primary source in a new tab.

  1. [nrel-demand-charge-survey]Identifying Potential Markets for Behind-the-Meter Battery Energy Storage: A Survey of U.S. Demand Charges (2017 summary brochure)National Renewable Energy Laboratory. Accessed 2026-09-12.
  2. [nwpcc-cannabis]Electricity Consumption from Northwest Cannabis ProductionNorthwest Power and Conservation Council. Accessed 2026-09-12.
  3. [santee-cooper-demand]Understanding Your Utility Demand and UsageSantee Cooper. Accessed 2026-09-12.
  4. [im-tariff-iurc]Indiana Michigan Power Company Tariff (demand ratchet provisions)Indiana Utility Regulatory Commission. Accessed 2026-09-12.
  5. [eia-glossary-l]Glossary: L (load, load factor)U.S. Energy Information Administration. Accessed 2026-09-12.
  6. [ercot-dr-overview-2023]Overview of Demand Response in ERCOT (April 2023 presentation)Electric Reliability Council of Texas. Accessed 2026-09-12.