Skip to content

Dehumidification Load in Indoor Cannabis Cultivation

Most of the water you irrigate with ends up in the room air within a day; published engineering estimates run from about 70 percent to 95 percent of irrigation volume, and manufacturer sizing rules put flowering canopy at roughly 0.5 to 2 pints per square foot per day. Removing that water is a latent load that ordinary air conditioners handle badly, so it gets its own equipment. A 5,000 square foot flower room can need several thousand pints a day of removal, which at typical efficiencies of 4 to 9 pints per kWh is hundreds of kWh a day and tens of kilowatts of demand.

By Jason Taken, Founder, Jaken Energy

Updated September 11, 2026

Where the water comes from

An indoor grow is a humidifier with a crop in it. Water goes onto the root zone, the plant pulls it up, and the leaves release most of it as vapor. Engineering estimates of that fraction vary with medium, irrigation practice, and how much runoff you capture: an HPAC Engineering analysis puts transpiration at about 70 percent of total irrigation water returned to the air [hpac-latent-2023], while Denver's cannabis energy guide says simply that the water applied to plants is transpired by the plants and then has to be removed from the space [denver-bmp-energy-2019]. Manufacturer sizing guidance converts that into a canopy rule of thumb of 0.5 to 2 pints of moisture per day for every square foot of canopy, with the grower adjusting for their own conditions [quest-dehum-101].

The transpiration math, step by step:

  1. Total daily irrigation in gallons.
  2. Multiply by 8 to get pints (1 gallon is 8 pints).
  3. Multiply by the transpired fraction. Use 0.7 for a conservative estimate of load, 0.9 or higher if you run hydroponics with little runoff, and check it against your own drain volumes.
  4. Note when it happens. Plants transpire mostly during lights-on, so a 12-hour photoperiod concentrates most of the daily water into 12 hours.

Southern California Edison's market study reports indoor flowering irrigation in the range of 0.096 to 0.16 gallons per square foot per day [sce-etp-2021]. At 0.13 gallons and an 80 percent transpired fraction, that is 0.13 × 8 × 0.8 = about 0.83 pints per square foot per day, comfortably inside the manufacturer rule of thumb.

Latent versus sensible: why this is a separate load

HVAC engineers split the work of conditioning a room into two parts. Sensible load is heat you can measure with a thermometer: fixture watts, motors, people, heat through the walls. Latent load is the energy tied up in water vapor. When a plant evaporates a pint of water it absorbs heat from the room to do it, converting sensible heat to latent heat and cooling the air while loading it with moisture [hpac-latent-2023]. That heat comes back out when a coil condenses the water.

Conventional air conditioners are built for buildings where most of the load is sensible. The HPAC analysis describes this with the sensible heat ratio, the share of a unit's capacity that goes to sensible cooling; most packaged equipment performs well at ratios of 80 percent and up, while grow rooms often operate well below that [hpac-latent-2023]. A plant-filled room can have more moisture to remove than heat, and a standard AC unit will overcool the space trying to wring the air out, then need reheat.

The lights-off period is where this bites. Fixtures are off, so sensible load collapses, but the plants are still respiring and the room is still wet. Denver's guide notes that the warmer the room can be kept during lights-off, the more efficiently dehumidification equipment operates [denver-bmp-energy-2019], which is why facilities that moved to LED and lost the free HPS heat sometimes add reheat. The HVAC sizing page covers equipment selection for low sensible heat ratios.

Equipment choices and what they cost to run

EquipmentHow it removes waterWhere it fitsEfficiency figures
Portable refrigerant dehumidifiersCool air on a coil to condense water, then reheat with the same refrigerantMost common choice in the facilities SCE surveyed [sce-etp-2021]; supplement to ACENERGY STAR Version 6.0 (effective October 1, 2025) requires at least 3.30 liters per kWh for portables of 50 pints per day and above, 2.01 for 25 to 50 pints, 1.70 at 25 pints and below [energystar-dehum-criteria]
Commercial overhead refrigerant unitsSame principle, ducted, larger compressorsStandalone dehumidification in flower rooms; multiple units per roomExample: Quest 506 rated 506 pints per day and 8.1 pints per kWh at 80 degrees F and 60 percent relative humidity, drawing 2,700 W [quest-506-spec]
Integrated HVAC with hot-gas or hot-water reheatAir handler overcools to condense, then reheats without a second energy sourceChilled-water and larger packaged systems [denver-bmp-energy-2019]Depends on system; avoids the overcool-and-electric-reheat penalty
Desiccant dehumidifiersAdsorb vapor onto a desiccant wheel, regenerate with heatLow-temperature or very low sensible-ratio spaces, drying roomsPerform independently of the space's sensible cooling requirement [hpac-latent-2023]; regeneration heat is the operating cost

Unit conversion for comparing the ENERGY STAR and manufacturer figures: 1 liter is about 2.1 pints, so 3.30 liters per kWh is roughly 7 pints per kWh and 2.01 liters per kWh is roughly 4.2. Note the rating conditions differ, so treat the comparison as approximate.

Two practical points. First, efficiency is quoted at a rating point and drops as the room gets cooler and drier, so a unit that reads 8 pints per kWh on the spec sheet does less in a 68 degree lights-off room. Second, oversizing is not free: a unit that short-cycles wastes the start-up energy of every cycle. Manufacturer guidance is to match capacity to actual canopy water loss and distribute several units rather than one large one [quest-dehum-101].

A worked example: a 5,000 square foot flower room

Every number here is an input we chose. Substitute your own irrigation logs and equipment specs.

Assumptions:

InputValueNote
Flowering canopy5,000 sq ft
Irrigation0.15 gallons per sq ft per dayInside SCE's reported 0.096 to 0.16 range [sce-etp-2021]
Transpired fraction80 percentBetween the 70 percent engineering estimate [hpac-latent-2023] and higher hydroponic figures
Equipment efficiency, two cases8 pints per kWh and 4.2 pints per kWhA commercial overhead unit at its rating point [quest-506-spec] and a mid-size portable at the ENERGY STAR floor [energystar-dehum-criteria]
Unit size506 pints per day, 2.7 kW[quest-506-spec]
Electricity price14.19 cents per kWhU.S. average commercial, June 2026 [eia-epm-5-6-a]
Demand charge12 dollars per kW-monthAssumed

Water load: 5,000 × 0.15 = 750 gallons per day = 6,000 pints. Times 0.8 = 4,800 pints per day to remove.

Equipment count: 4,800 ÷ 506 = 9.5 units at nameplate. With a 25 percent margin for post-irrigation spikes and derating in lights-off, plan on 12 units.

Energy, efficient case: 4,800 ÷ 8 = 600 kWh per day, about 18,000 kWh a month. At 14.19 cents: about 2,550 dollars a month.

Energy, portable case: 4,800 ÷ 4.2 = 1,140 kWh per day, about 34,300 kWh a month, about 4,870 dollars a month.

Demand: if all 12 overhead units run at once, 12 × 2.7 kW = 32 kW. At 12 dollars per kW that is about 390 dollars a month, and more importantly it lands on top of the lighting peak if the units all start after lights-on. See demand charges explained.

The gap between the two energy cases, roughly 2,300 dollars a month for one 5,000 square foot room, is the cost of equipment choice alone, before any change in the water load. Reducing irrigation runoff, tightening the envelope so outside humidity stays outside (see weatherization and building envelope), and raising lights-off temperature all reduce the load itself. The facility energy cost calculator lets you run the whole facility.

How it shows up on the bill

Dehumidification is invisible on a utility bill because there is no line for it. It shows up in three places:

  • Around-the-clock kWh. Lights run 12 hours; dehumidifiers run 24. In the Northwest Council's producer survey, cooling was 15 percent of total facility electricity, with ventilation, dehumidification, and pumps making up most of the rest of the 33 percent non-lighting share [nwpcc-cannabis]. Facilities in humid climates report higher shares; Denver's guide says climate control can be 50 percent or more of an indoor facility's consumption [denver-bmp-energy-2019], and the Colorado State life-cycle study found HVAC held the largest energy demand once local climate was included [summers-2021].
  • Demand. Compressors starting together after irrigation or lights-on set the interval peak. Staggering unit start-ups by a few minutes and sequencing irrigation across rooms spreads the load across intervals.
  • Load factor. Because it runs in both photoperiods, dehumidification raises the ratio of average to peak load, which suppliers price favorably. A facility with a flatter profile gets a better fixed-price quote than one with a spiky one, all else equal.

For the whole-facility view, the kWh per square foot benchmarks page shows how lighting and HVAC split in published surveys, and the LED vs. HPS page explains why cutting lighting watts changes the sensible load a lot and the latent load hardly at all.

Sizing from a rule of thumb is a starting point, not a design

The pints-per-square-foot rule and the transpired-fraction estimate can each be off by half in either direction for a specific facility. Log irrigation and drain volumes for a full cycle, and have a mechanical engineer size equipment from measured data before you buy.

Frequently asked questions

How many pints per day does a flowering room produce?

Start from irrigation. Multiply gallons applied per day by 8 to get pints, then by the share that transpires, which published estimates put between about 70 and 95 percent. Manufacturer rules of thumb land at 0.5 to 2 pints per square foot of canopy per day. A room with heavy irrigation and high light sits at the top of that range.

Why can't my air conditioner just handle the humidity?

It can, but inefficiently. A cooling coil only condenses water after it has cooled the air to the dew point, so removing moisture with an AC unit means overcooling the room and then reheating it. Equipment built for high latent loads, whether standalone refrigerant dehumidifiers or desiccant systems, removes water without that penalty.

Is a dehumidifier's pints-per-day rating the same at every temperature?

No. Capacity and efficiency both depend on the air conditions at the inlet. Manufacturers rate commercial units at a stated condition, often 80 degrees F and 60 percent relative humidity, and the number falls in a cooler, drier room. Compare units at the same rating point and expect less in lights-off.

Does switching to LED reduce dehumidification load?

Not much. Transpiration follows light intensity, temperature, and vapor pressure deficit, so at the same PPFD the plants release about the same water. What changes is the sensible heat, which falls a lot. Rooms that lose HPS heat sometimes need reheat in lights-off so the dehumidifiers keep working in their efficient range.

How does dehumidification show up on my bill?

As kWh around the clock and as kW in the demand charge. Unlike lights, dehumidifiers run in both photoperiods, and they cycle on together after irrigation and after lights-on. On a demand tariff, a bank of units starting in the same 15-minute window adds directly to your billed peak.

About the author
Jaken Energy

Jason Taken founded Jaken Energy, the commercial energy procurement practice behind this site. He works with licensed cannabis operators in deregulated electricity markets to lower supply rates, manage demand charges, and evaluate efficiency upgrades.

Sources

Inline citations in this article, such as [hpac-latent-2023], refer to the entries below. Links open the primary source in a new tab.

  1. [hpac-latent-2023]Latent Loads Matter: HVAC for Cannabis Grow Facilities (David Schurk, August 3, 2023)HPAC Engineering. Accessed 2026-09-11.
  2. [quest-dehum-101]Dehumidification 101 for Cannabis GrowersQuest Climate. Accessed 2026-09-11.
  3. [quest-506-spec]Quest 506 Dehumidifier specificationsQuest Climate. Accessed 2026-09-11.
  4. [denver-bmp-energy-2019]Cannabis Environmental Best Management Practices Guide: Energy (2019)City and County of Denver, Department of Public Health and Environment. Accessed 2026-09-11.
  5. [energystar-dehum-criteria]Dehumidifiers Key Efficiency Criteria (Version 6.0, effective October 1, 2025)U.S. EPA ENERGY STAR. Accessed 2026-09-11.
  6. [sce-etp-2021]Indoor Cannabis Market Characterization, Emerging Technologies Program report ET20SCE8030 (April 2021)Southern California Edison. Accessed 2026-09-11.
  7. [nwpcc-cannabis]Electricity Consumption from Northwest Cannabis Production (survey analysis of 2017 Oregon and Washington licensed canopy)Northwest Power and Conservation Council. Accessed 2026-09-11.
  8. [summers-2021]Insatiable demand for cannabis has created a giant carbon footprint (news release on Summers, Sproul and Quinn, Nature Sustainability, 2021)EurekAlert / Colorado State University. Accessed 2026-09-11.
  9. [eia-epm-5-6-a]Electric Power Monthly, Table 5.6.A: Average Price of Electricity to Ultimate Customers by End-Use Sector, by State, June 2026 and June 2025U.S. Energy Information Administration. Accessed 2026-09-11.