Submetering for Multi-Tenant Cannabis Cultivation Buildings
In a building where several licensees share one utility meter, the landlord gets one bill and has to divide it. Submeters measure each tenant's kWh and kW so the split follows actual use instead of square footage, but the moment a landlord bills tenants for electricity, state utility law gets involved. Regulators in New York, Texas, and Ohio all treat resale of electricity as something they can police, usually by capping what the tenant pays at what the utility would have charged. Done right, submetering also gives each operator the interval data they need to negotiate their own rate.
By Jason Taken, Founder, Jaken Energy
Updated September 12, 2026Master meter versus submeter
A master-metered building has one utility service, one meter, one account, and one bill, addressed to the landlord. The utility knows nothing about the tenants. Whatever the tenants pay for electricity, they pay to the landlord under the lease.
A submeter is a second meter installed behind the utility's meter, on the feeder that serves one tenant, one room, or one piece of equipment. It measures the same things a utility meter measures, kilowatt-hours and, if it is an interval meter, kilowatts by 15-minute window. The utility does not read it, bill from it, or care that it exists. Its only job is to make the landlord's division of the single bill follow actual use.
Cannabis buildings end up master-metered for ordinary reasons. A warehouse was built with one 2,000 A service and later carved into four licensed suites. A cultivator sublets a flower room to a craft grower. A landlord converts a building for several tenants and does not want four utility deposits, four transformers, and four sets of utility easements. None of that is a problem until the bill arrives, because a cultivation bill is large and lumpy. In the Northwest Power and Conservation Council's producer survey, lighting alone was 66 percent of facility electricity and flowering rooms 49 percent [nwpcc-cannabis]. A tenant running a flower room and a tenant running a trim and packaging suite on the same square footage use electricity at very different rates, and a square-footage split will get one of them badly wrong.
Three ways to divide a shared bill
Square footage. Simple, common, and almost always unfair in a cultivation building. It assumes every square foot uses the same electricity. A 5,000 square foot flower room at 35 W per square foot draws 175 kW when lit; a 5,000 square foot dry and cure space draws a tiny fraction of that. The flower tenant is subsidized; the dry-room tenant pays for lights they do not own.
Connected load. The landlord adds up each tenant's nameplate kW and splits the bill in proportion. Better, because it tracks lights and HVAC, but nameplate is not use. A tenant with two rooms on opposite photoperiods never runs all of its connected load at once, while a tenant with one big room on a single timer does.
Submetered use. Each tenant's kWh is measured. The energy portion of the bill is split by measured kWh. The demand portion is split by measured kW, ideally by each tenant's contribution to the building's single billed interval. Taxes, fixed customer charges, and common-area loads are split by an agreed formula. This is the only method under which a tenant who cuts its own use sees its own bill fall.
A worked comparison, with every number chosen for illustration:
Inputs (assumed): a building with two tenants of equal square footage. Tenant A runs a lit flower room, 175 kW peak, 63,000 kWh a month. Tenant B runs processing and packaging, 40 kW peak, 20,000 kWh a month. The utility bills 83,000 kWh at 13.77 cents, Ohio's June 2026 average commercial price [eia-epm-5-6-a], plus a delivery demand charge we set at 12 dollars per kW on a coincident peak of 205 kW (assume 10 kW of B's load happens to be off at A's peak). Energy: 11,429 dollars. Demand: 2,460 dollars. Total 13,889 dollars.
| Method | Tenant A pays | Tenant B pays | Comment |
|---|---|---|---|
| Square footage (50/50) | 6,945 | 6,945 | B pays 3,300 more than its use justifies |
| Connected load (175/40) | 11,304 | 2,585 | Close on energy, but ignores when loads coincide |
| Submetered kWh and coincident kW | 8,675 energy + 2,100 demand = 10,775 | 2,754 energy + 360 demand = 3,114 | Each tenant pays for what its meter shows |
The submetered result differs from the connected-load result by only a few hundred dollars here because we chose simple loads. In a real building with staggered photoperiods, a tenant whose lights are off during the building's peak interval can be paying thousands in demand it did not cause.
What revenue-grade means, and why it matters when money changes hands
The meters utilities bill from are built and tested to ANSI C12.1, the American National Standard code for electricity metering, which establishes acceptable performance criteria for watthour meters, demand meters, and related devices and describes acceptable in-service performance levels for meters used in revenue metering [ansi-c12-1-2022]. "Revenue-grade" in a product sheet means the manufacturer claims the meter meets that code's accuracy class. It does not mean the installation does. A revenue-grade meter fed by the wrong current transformer ratio, or wired to a feeder that also carries a neighbor's dehumidifiers, will produce a confident, precise, wrong number.
Three practical points for landlords and tenants:
- Match the CT ratio and the feeder. Most disputes we hear about trace to a current transformer programmed for the wrong ratio or clamped on a feeder that serves more than one tenant. Get a single-line diagram and confirm which breaker feeds which meter.
- Get interval capability. A kWh-only submeter can split energy. Only an interval meter can split demand fairly, and demand can be 30 to 70 percent of a commercial bill depending on the tariff; see demand charges explained.
- Put testing in the lease. Who owns the submeter, who calibrates it, how often, and what happens when it is found out of tolerance. New York's submetering rules, written for residential buildings, require the submeterer to credit overcharges with interest [ny-16-nycrr-96-6]; a commercial lease should say the same thing on purpose.
State rules on reselling electricity
Here is the part landlords often miss. In most states, selling electricity to the public is what makes a company a utility, and utilities are regulated. A landlord who meters and bills tenants for power is, in the eyes of several commissions, reselling electricity, and the commissions have said so.
New York. The Department of Public Service is explicit that a building owner who submeters becomes the distribution utility to its residents, with the rights and responsibilities that go with it, and must first petition and receive authorization from the Public Service Commission before submetering [ny-dps-submetering]. Residents will never pay more than what the local distribution utility charges [ny-dps-submetering], and the regulation itself states that the submeterer shall not charge more than the applicable rate cap [ny-16-nycrr-96-6]. These rules, in 16 NYCRR Part 96, are written for residential submetering; the Department's page does not address commercial tenants [ny-dps-submetering]. That is the state's position on the principle, and commercial landlords should not assume the principle stops at the residential line without asking.
Texas. The Public Utility Commission's rule on master-metered utilities provides that an apartment house owner may not impose additional charges on a tenant in excess of the actual charges imposed on the owner for utility consumption, and it names the acceptable allocation methods, square footage or individually metered or submetered usage, with any other method requiring commission approval [tx-25-141]. The rule applies to apartment houses [tx-25-141]. Texas is also the state where a large cultivation tenant can bypass the whole question by taking its own service and shopping for a retail electric provider; see what is energy deregulation.
Ohio. In April 2026 the Supreme Court of Ohio held that Nationwide Energy Partners, a company that bought electricity from AEP and resold it to apartment tenants, is a public utility subject to regulation by the Public Utilities Commission of Ohio [ohio-sc-nep-2026]. The court's reasoning was plain: tenants who purchase electricity are consumers of electricity and NEP is in the business of supplying it [ohio-sc-nep-2026]. The opinion noted that NEP's margin came from paying AEP's lower commercial rate and reselling at a higher residential rate, and that NEP had agreed not to charge more than AEP's default residential rate [ohio-sc-nep-2026]. The Ohio Consumers' Counsel, which had argued that submetered consumers lacked rate regulation, complaint procedures, standardized billing, and the ability to shop for supply, reports that PUCO is now implementing oversight in two open cases [ohio-occ-submetering].
The pattern across all three: regulators do not object to submetering as a measurement tool. They object to a middleman making a margin on electricity, and their remedy is a cap at the utility's own price plus, in New York and now Ohio, a requirement to submit to commission oversight. Nearly all of the published rules concern residential tenants. Commercial cannabis tenants are rarely named in them, which cuts both ways: a landlord may have more freedom, and a tenant may have fewer protections. Confirm with your PUC or counsel before the lease is signed, not after the first disputed bill.
A landlord who adds a percentage to the utility's price, or an "energy management fee" per kWh, is doing the thing the Ohio court and the New York and Texas rules address. A flat, disclosed administrative charge for reading meters and issuing statements is a different matter and is the usual compromise. Do not rely on this page as legal advice; confirm with your regulator or advisor.
How submetering supports your own negotiations
A tenant in a master-metered building has no utility account, so it cannot enroll with a competitive supplier, change rate class, or enroll in demand response on its own. What it can do is use its submeter data.
- Argue the allocation. Twelve months of interval data shows exactly when your load peaks relative to the building's billed peak. If your lights are off during the building's worst interval, you have a documented case that you should not be paying a proportional share of the demand charge.
- Price a separate service. The utility will quote a new service and a rate class based on your measured load, not the building's. A 175 kW tenant may land in a class with a lower per-kW demand rate than the 800 kW building sits in; see utility rate classes explained.
- Give the landlord a reason to shop. In a choice state, the landlord holds the account and can sign a supply contract for the whole building. Tenants with interval data can show the landlord what a fixed or block-and-index product would do to each tenant's cost, which is usually the argument that gets the landlord to make a call; see energy broker vs. direct supplier.
- Benchmark yourself. Your kWh per square foot of canopy, from your own meter, is what lets you compare your operation against published ranges in kWh per square foot benchmarks instead of guessing from a share of someone else's bill.
- Read the whole bill. Ask for the utility's actual bill, not just the landlord's statement. The line items on understanding your commercial utility bill tell you whether a ratchet, a power factor penalty, or a rate class you never chose is inside your "share."
A short checklist before you sign a multi-tenant lease
- Ask which meter is the utility's and which are submeters, and get the single-line diagram.
- Ask for the allocation formula in writing, with a sample month worked out.
- Confirm the per-kWh and per-kW you will pay equals the utility's tariff, with any administrative fee shown separately.
- Confirm the submeter is interval-capable and who owns the data.
- Confirm the state's position on resale for your tenant type with the PUC or counsel.
- Ask the utility, not the landlord, what a separate service for your load would cost and which rate class it would fall in.
Submetering is a measurement decision that turns into a regulatory one the moment a dollar figure follows it. Handle both on purpose.
Frequently asked questions
Can my landlord charge me more per kWh than the utility charges them?
In most states that have addressed it, no. New York caps a submeterer's rate at what the local utility would charge, Texas bars an owner from imposing charges in excess of the actual utility charges, and Ohio's Supreme Court ruled in 2026 that a company reselling electricity to tenants is a public utility subject to PUCO. Rules were written mostly for residential buildings, so confirm how your state treats commercial tenants with the PUC or counsel.
Is a submeter the same as a utility meter?
Physically similar, legally different. The utility's meter is the billing point for the utility's tariff. A submeter sits behind it, is owned by the landlord or tenant, and only matters for how the building's single bill is divided. It does not create a utility account, and the utility will not read it or bill from it.
What does revenue-grade mean?
It means the meter meets the accuracy and performance criteria in ANSI C12.1, the code for electricity metering that utilities themselves use for revenue meters, and that it is installed and tested so its reading can be relied on for billing. A power monitor in a control panel is usually not revenue-grade, and a landlord billing from one is inviting a dispute.
How should demand charges be split between tenants?
By coincident demand if you have interval submeters, and by agreement if you do not. The utility bills the building's single highest interval; a tenant whose lights are off during that interval did not cause it. Without interval data, landlords fall back to square footage or connected load, which is simple but punishes the tenant with the flattest load.
Can a submetered tenant shop for a competitive supplier?
Not directly. Supplier enrollment attaches to the utility account, and there is only one, held by the landlord. The landlord can shop for the whole building and pass the price through, or a tenant can push for a separate utility service. Interval data from a good submeter is what makes either conversation productive.
What should the lease say about electricity?
The allocation method, what the tenant pays per kWh and per kW, whether the landlord may add an administrative fee, who owns and calibrates the submeters, how often they are tested, what happens when the utility bill has a ratchet or a rate class change, and how disputes are resolved. A lease that says only 'tenant pays its share of utilities' is where most fights start.
Related reading
- Demand Charges Explained for Cannabis Cultivators
What a demand charge is, how utilities measure peak kW in 15- or 30-minute windows, why grow rooms get hit hard, how ratchets work, and a worked example.
- Understanding Your Commercial Utility Bill (Line-Item Breakdown)
Supply vs delivery, customer charge, distribution demand, transmission, capacity, riders, power factor, and taxes, with an annotated sample bill for a grow.
- Interval Data & AMI Meters: Using Your Data to Negotiate Better Rates
How to pull 15-minute interval data via Green Button, read your load shape, see how suppliers price load factor, and know what to send a broker.
- Utility Rate Classes Explained: Small Commercial, Large Commercial, C&I
How utilities assign small, large, and C&I rate classes by peak kW, why the wrong class costs money, real tariff examples, and how to request a class review.
- Multi-State Operator (MSO) Energy Procurement Strategy
How a multi-state cannabis operator buys power as a portfolio: ISO differences, staggered contract expirations, aggregation, data standards, and governance.
- New Facility Build-Out Utility Questions for Cannabis Grows
When to call the utility, service sizing, line extensions, supply contracts before energization, California DA notice, rate class, and state energy reporting.
- Contract Fine-Print Questions for Cannabis Electricity Supply
Early termination fees, bandwidth and swing clauses, evergreen auto-renewal, usage drops, assignment on sale, pass-throughs, and meter vs entity rules.
Jason Taken founded Jaken Energy, the commercial energy procurement practice behind this site. He works with licensed cannabis operators in deregulated electricity markets to lower supply rates, manage demand charges, and evaluate efficiency upgrades.
Sources
Inline citations in this article, such as [ohio-sc-nep-2026], refer to the entries below. Links open the primary source in a new tab.
- [ohio-sc-nep-2026]Submetering Company Subject to Regulation by PUCO as a Public Utility (In re Complaint of Ohio Power Co. v. Nationwide Energy Partners, decided April 22, 2026) — Supreme Court of Ohio, Court News Ohio. Accessed 2026-09-12.
- [ohio-occ-submetering]Submetering (consumer information page) — Office of the Ohio Consumers' Counsel. Accessed 2026-09-12.
- [ny-dps-submetering]Electric Submetering Information — New York State Department of Public Service. Accessed 2026-09-12.
- [ny-16-nycrr-96-6]16 NYCRR 96.6, Electric submetering service conditions — New York Codes, Rules and Regulations (via Legal Information Institute). Accessed 2026-09-12.
- [tx-25-141]16 Tex. Admin. Code 25.141, Central System or Non-Submetered Master Metered Utilities — Public Utility Commission of Texas (via Legal Information Institute). Accessed 2026-09-12.
- [ansi-c12-1-2022]ANSI C12.1-2022, American National Standard for Electric Meters: Code for Electricity Metering (contents and scope) — National Electrical Manufacturers Association. Accessed 2026-09-12.
- [nwpcc-cannabis]Electricity Consumption from Northwest Cannabis Production (survey analysis of 2017 Oregon and Washington licensed canopy) — Northwest Power and Conservation Council. Accessed 2026-09-12.
- [eia-epm-5-6-a]Electric Power Monthly, Table 5.6.A: Average Price of Electricity to Ultimate Customers by End-Use Sector, by State, June 2026 and June 2025 — U.S. Energy Information Administration. Accessed 2026-09-12.